Pages Header Banner 2
Pages Header Banner 1
Pages Header Banner 3

Toll Free: 1.800.387.2840

Terms & Conditions

Frequently Asked Questions

What is a Zig-Zag Grounding Transformer?

A Zig-Zag grounding transformer is a special three phase autotransformer with no secondary or output. It is used to establish a neutral on a 3 wire system. There are several reasons why a zig zag autotransformer may be used include ground fault protection, neutral grounding (solid or via a resistor), and harmonic filtering.

What is an Isolation Transformer?

All transformers other that autotransformers are Isolation Transformer. This is due to the fact that the primary and secondary windings are electrically isolated from each other (they are not physically connected to each other). The transformation in voltage and current between primary and secondary windings occurs as a result of the shared magnetic field in the core (Mutual Inductance).

What is an Autotransformer?

An autotransformer is a transformer that has only one winding per phase, part of which is common to both the primary and secondary circuits. Transformers wired in a “Buck-Boost” configuration are autotransfomers. Autotransformers are designed to adjust the supply voltage when isolation from the line is not necessary and where local electrical codes permit. An autotransformers can be used in either a step-up or step-down application unlike isolation transformers. Autotransformers can also be used as part of a reduced voltage starter to reduce motor inrush current (see Motor Starting Autotransformers)

What are the standard service conditions for a dry type distribution transformer?

Unless designed for special service conditions / environments, below are the standard service conditions for dry type distribution transformers:

  • Ambient Temperature: -40°C to + 30°C (max peak +40°C)
  • Relative Humidity: < 70%
  • Altitude: ≤ 1000m ASL (3300 ft.)

Avoid rain, moisture, high temperature, intense heat or direct sunlight. Maintain the minimum recommended clearances and ensure that all ventilated panels are clear of obstructions.

What is temperature rise?

Temperature rise refers to average increase of temperature of the transformer windings at full load above the ambient temperature. These is also a “hot spot” temperature, which refers to the hottest temperature at any specific point in the transformer winding. For example, distribution transformer with a 220°C insulation system would typically be designed with a 150°C average temperature rise and a + 30°C hot spot allowance. Above a 40C ambient, the total absolute temperature will not exceed 220°C. Transformers with lower temperature insulation systems (180°C or 200°C) will be designed with lower temperature rises (115° or C130°C) and hot spots so they can be installed in the same ambient temperature and still not exceed the temperature rating of the insulation system. See table below with the maximum average winding temperature rise, maximum hot spot temperature rise and maximum winding temperature for the most common insulation ratings. Note that these are based on a max average ambient of 30°C during any 24-hour period and a maximum ambient of 40°C at any time.

Insualation Rating Insulation Class Average Winding
Temperature Rise
Hot Spot
Temperature Rise
Maximum Winding
Temperature
Class 180 F 115°C 145°C 180°C
Class 200 N 130°C 160°C 200°C
Class 220 H 150°C 180°C 220°C

Customers often request lower than the average temperature rise values shown in the table above. The lower average temperature rise can offer the following benefits:

  • The transformer can be installed in higher ambient temperatures without overheating beyond what the insulation is designed for.
  • The transformer can be expected to have a longer operational life with lower MTBF.
  • The transformer can handle continuous overloads and higher short time overloads without overheating beyond what the insualation is designed for.

What are the storage requirements for a dry type transformer?

Any transformer which is not installed and energized immediately should be stored in a dry, clean space having a uniform temperature to prevent condensation on the windings. Dry type transformers with resin dipped or epoxy vacuum impregnated coils can be stored at ambient temperatures as low as -50C. Transformers with encapsulated or epoxy cast coils should not be stored at ambient temperatures below -20C to prevent cracking of the epoxy. Preferably, transformers should be stored in a heated building having adequate air circulation and protected from cement, plaster, paint, dirt, and water or other gases, powders, and dust. The floor on which the transformer is being stored should be resistant to the upward migration of water vapor. Precautions should be taken to prevent storage in an area that water could be present, such as roof leaks, windows, etc. Condensation or absorption of moisture can be greatly reduced by keeping the transformer enclosure 5⁰C-10⁰C above ambient temperature. This can be easily achieved by the installation and energization of space heaters (optional). If the transformer is not furnished with internal space heaters, then external, portable heaters can be used. Note: Lamps or heaters should never come in direct contact with the transformer coil insulation.

It is not advisable to store a dry type transformer outdoors, but in the case that it is unavoidable, protective measures should be taken to prevent moisture and foreign debris from entering the transformer enclosure. The plastic wrapping supplied during shipment should be left in place, and a suitable drying agent such as silica gel packs should be used. The unit should also be checked periodically for indications of condensation on the windings, coil support blocks, core, core clamping system and bus/cables.

What is required clearance around a dry type distribution transformer?

The minimum required clearances of a dry type transformer to walls, floors or other equipment must adhere to the local electrical code requirements.

In the absence of such requirements, Rex Power Magnetics recommends that dry type transformers be mounted so that there is an air space of no less than 150mm (6”) between the enclosures, and between the enclosure and any adjacent surface except floors. When the adjacent surface is a combustible material, the minimum permissible separation between the transformer enclosure and the adjacent surface should be 300mm (12”). Where the adjacent surface is the wall on which the transformer is mounted, the minimum permissible separation between the enclosure and the mounting wall should be 6mm (0.25”) so long as the surface is of a non-combustible material.

What do I need to consider for transformers energized at low ambient temperatures?

In Dry Type Transformers, the air inside and surrounding the enclosure are a critical part of the transformer’s function. Low ambient temperatures generally do not adversely impact an energized transformer, as the energization (no-load) losses typically generate enough heat to maintain appropriate conditions, in low ambient temperatures as low as -40 °C.

There are two main issues with energizing transformers which have been stored at low ambient temperatures:

  • The insulation in the coils can become brittle at low temperatures. The expansion of the conductors after loading a transformer from a cold start, or the contraction of the conductor during storage at lower temperatures can lead to a crack in the insulation between turns or between layers, leading to an internal fault.
  • Low ambient temperatures can lead to condensation forming within the transformer enclosure, as well as on and inside the transformer coils. Energizing a transformer with condensation on the coils can result in an internal fault and damage to the insulation.

Rex's installation, operation and maintenance manuals recommends that transformers be tested (meggered), brought above 0°C and/or go through a dry-out process if moisture is suspected to be present. Refer to REX's cold start procedure when energizing a transformers below 0 °C.Damage and injury can result from energizing a transformer which has had its insulation system compromised due to moisture.

What is the terminal temperature rating of ventilated dry type distribution transformers?

Rex Power Magnetics’ ventilated distribution transformer terminals are rated 90°C. Conductors with at least a 90°C insulation rating at or below their 90°C ampacity rating should be utilized.

What is the odor emitting from my new transformer? 

It`s normal for new transformers to release some harmless odors from the varnish impregnation used in the coils for a week or two after energization. Older Transformers can also release some odor if loaded to a higher level than they have experienced previously in their history.

What is the life expectancy of dry type transformers 

The minimum life expectancy of a dry type transformers is primary dependent on the insulation life vs. temperature relationship, designated as minimum life expectancy in IEEE Std C57.12.56. Other factors such as humidity/condensation, short circuit events, sustained overloads, and other external factors can cause a dry type transformer to fail prematurely, however those are outside the normal operating conditions of the transformer and are not considered in the design life expectancy.

Aging or deterioration of insulation is a function of time and temperature and described in detail in IEEE Std. C57.96. Since, in most transformers, the temperature is not uniform, the part that is operating at the highest temperature will ordinarily undergo the greatest deterioration. Therefore, aging studies consider the aging effects produced by the highest temperature.

Based on the insulation life expectancy curves outlined in IEEE Std C57.96, all of Rex Power Magnetics’ dry type transformers utilize a UL listed insulation system with a maximum hot spot temperature that will provide a design life expectancy of a minimum of 30 years under continuous rated load, and standard ambient temperature conditions. For transformer with a reduced average and hot spot temperature rise, this design life expectancy exceeds 50 years.

Can a transformer be connected in reverse (back fed)?

In general, dry type transformers can be connected in reverse (back fed) however there are several precautions that should be considered:

  • Compensated Windings: Control transformers and distribution transformers below 3kVA are typically designed with an overvoltage on the secondary to compensate for voltage regulation at full load. Reverse feeding these transformers may lead to a lower than expected output voltage.
  • Inrush current: The inrush current when energizing a transformer from the intended secondary terminals will be significantly higher than on the primary side as a multiple of the rated current. This high inrush current can cause nuisance tripping of the protective breaker and special considerations may need to be made.
  • Voltage Taps: Given that there are typically no voltage adjustment taps on the secondary side, the transformer cannot be adjusted to account for higher or lower than nominal incoming voltages. In order to not damage the insulation or overexcite the core, the input voltage should not exceed the nominal rated voltage. Under voltage conditions are ok, and the taps on the primary winding can be used to boost the output voltage
  • Grounding: When the secondary (wye) of a delta-wye transformer is energized instead of the primary (delta), then the wye side of the transformer is not a separately derived service. As such, the neutral should not be connected to building ground nor should it be bonded to the transformer enclosure

Always review applicable codes and standards and consult with the local authority having jurisdiction before reverse feeding transformers.


R.C. Snubber

Product Overview & Application

SNUBBER open FrontR.C. snubbers are a passive electrical devices, comprised of appropriately selected resistors and capacitors, which are used for protecting medium voltage power transformers from electrical switching transients. While lightning arresters help protect the transformers from the high voltage spikes that appear on the line after a lightning strike, snubbers are better suited for the more common problem of circuit breaker switching transients. Examples of the switching operation include instances where a circuit breaker switches between transformer primaries, or automatically triggered switching between grid and reserve power.

When a circuit breaker interrupts current flow, an arc develops across its contacts. The rapid current interruption usually occurs somewhere other than the current zero-crossing point, giving rise to a Transient Recovery Voltage (TRV), which has significant high-frequency content. If the transients are at the natural resonance frequency of the system, then there is a possibility of internal oscillatory voltages developing in the primary windings of the transformer. A high turn-to-turn voltage will result, which will lead to damage of the insulation.

The problem is further exasperated with modern vacuum-type circuit breakers, which have shorter distances between contacts. This serves to increase the speed of the interrupting cycle. The transient level and frequency are functions of the physical distance between the breaker and transformer, transformer construction, the type of load being switched, and the switching characteristic of the breaker.

The RC-snubber network lowers the frequency of the transient voltage applied to the transformer primary below the resonance frequency of the circuit. It reduces the development of the oscillatory voltages and provides a low impedance path to ground for the transients.

Snubbers are a low cost means for protecting a transformer against a costly repair and related downtime. In designing medium voltage power systems, it is a good practice to at least leave space for future installation of a snubber network.

Product Specification

Voltage Class  2.4kV to 34.5kV (150kV BIL)
Frequency  60Hz (50/60Hz Optional)
Fuse  6A Full Range Current Limiting Fuse
Resistor  20 - 50 Ohm (+/- 10%) Tubular Non-Inductive Resistor
Capacitor  0.13uF, 0.25uF, 0.5uF Surge Capacitor
Enclosure Type  Type 1 Indoor
Enclosure Finish  ANSI/ASA 61 Grey
Mounting  Floor Mounting
Warranty  12 Months (See Warranty and Limitations)
Quality System  ISO 9001:2015 Quality Management System
Optional Features & Accessories
  • Snubber Ground Current Monitoring Circuits
  • Distribution, Intermediate or Station Class Surge Arresters
  • Voltage Indicators / Glow Tubes
  • Type 1, 3R or 4X Enclsoure
  • 304 & 316L Stainless Steel Enclosure
  • Custom Enclosure Finish (Color)

Documentation


Canadian Sales Representatives

Alberta

Northern Alberta

Brodwell Industrial Sales
7 Rowland Cres
St.Albert ,AB T8N 5B3 
Tel: 780.458.1500
https://www.brodwell.com

Southern Alberta

Brodwell Industrial Sales
#1010, 4385 104 Ave SE
Calgary, AB T2C 5C6
Tel: 403.253.7702
https://www.brodwell.com

British Columbia

Arbutus West Agency Ltd.
1424 Regan Ave
Coquitlam, BC V3J 3B5
http://www.arbutuswest.com
E-mail: sales@arbutuswest.com
Tel: 604-521-5180

Manitoba

Integra Agencies Man. Ltd.
301 E Weston Street
Winnipeg, MB R3E 3H4Tel: 204-694-1339
E-mail: info@IntegraAgencyltd.mb.ca
http://www.integraagencyltd.mb.ca

New Brunswick

ELP Marketing
32 McQuade Lake Crescent
Halifax, NS B3S 1G8
Tel: 902-450-5155
http://www.elp.ns.ca
E-mail: quotesind@elp.ns.ca

Newfoundland & Labrador

Vigilant Technical Sales Ltd.
140 Cambell Avenue
St.John's, NL A1E 2Z8
Tel: 709-753-6685
http://www.vigilanttechnicalsales.ca
E-mail: matt@vigilanttechnicalsales.ca

Northwest Territories

No Sales Rep - Please contact our inside sales team.
Tel: 906-695-8844 ext: 2351
Toll Free: 1-800-387-2840 ext: 2351
E-mail: sales@arexpowermagnetics.com

Nova Scotia

ELP Marketing
32 McQuade Lake Crescent
Halifax, NS B3S 1G8
Tel: 902-450-5155
http://www.elp.ns.ca
E-mail: quotesind@elp.ns.ca

Nunavut

No Sales Rep - Please contact our inside sales team.
Tel: 906-695-8844 ext: 2351
Toll Free: 1-800-387-2840 ext: 2351
E-mail: sales@arexpowermagnetics.com

Ontario

Southern Ontario

Ontech Sales Inc.
1892 Baseline Rd. W.
Courtice, ON L1E 0X6
Darrell Mcneill: djmcneill@rogers.com 
Tel: 416-576-5114 
Lynn Konowal: lynnkonowal@rogers.com 
Tel: 905-828-4730 

Northern Ontario (Thunder Bay, Ft. Francis, Terrace Bay)

Integra Agencies
301 E Weston Street
Winnipeg, MB R3E 3H4
Tel: 204-694-1339
http://www.integraagencyltd.mb.ca

Prince Edward Island

ELP Marketing
32 McQuade Lake Crescent
Halifax, NS B3S 1G8
Tel: 902-450-5155
http://www.elp.ns.ca
E-mail: quotesind@elp.ns.ca

Quebec

Québec - Estrie, Centre du Québec & Mauricie

Agence Béliveau Turmel et Associés
57 Chemin Mountain
Bolton-Est, QC J0E 1G0
www.agencebta.com
Tél: 450-532-3578
Cell: 819-239-6591 
E-mail: jean-francois.despres@agencebta.com

Québec - Rive-Sud de Montréal, Abitibi

Eric Turmel
Tél: 450-349-7453
Cell: 514-515-7453
E-mail: eric.turmel@agencebta.com

Québec - Montréal, Laval, Laurentides, Outaouais & Lanaudière

Eric Massé
Cell: 514-247-1909
E-mail: eric.masse@agencebta.com

Québec - Québec, Saguenay, Cote-Nord, Beauce, Gaspesie & Bas St-Laurent

Serge Maheu
Cell: 418-933-4513
E-mail: serge.maheu@agencebta.com

Québec - Coordonnateur Technique

Stephane Brouillette
Cell: 438-300-8801 #101
E-mail: stephane.brouillette@agencebta.com

Québec - Support Interne

Yanick Turmel
Tél: 438-300-8802 #106 
E-mail: yanick.turmel@agencebta.com
 
Chanel Fournier 
Tél: 438-300-8802 #109
E-mail: chanel.fournier@agencebta.com

Saskatchewan

Advance Electrical Agency Ltd.
2717B Wentz Ave.
Saskatoon, SK S7K 4B6
Tel: 306-653-0313
https://www.advanceagency.net
E-mail: sales@advanceagency.net

Yukon

No Sales Rep - Please contact our inside sales team.
Tel: 906-695-8844 ext: 2351
Toll Free: 1-800-387-2840 ext: 2351
E-mail: sales@arexpowermagnetics.com

AC Line / Load Reactor

Inductors placed at the input and output of electrical equipment can provide protection and improve performance. Line Reactors absorb many power line disturbances which could damage or shut down your inverters, order variable speed controllers, or other voltage-sensitive equipment.

 

Read more: AC Line / Load Reactor


General Purpose Isolation Transformer

transformerGeneral Purpose Isolation transformers are used to lower distribution voltages (480 or 600V) to lower voltages (typically 120/240 or 208Y120) for power distribution within commercial or industrial buildings. These “two windings” transformers provide the electrical isolation required, and allow for short runs of high current, low voltage cables, reducing losses in the system, and reducing costs.

 

Read more: General Purpose Isolation Transformer


Mini Power Center

4-1Mini Power Centers combine three individual components, prewired into one NEMA 3R enclosure: a primary main breaker, a single-phase or three-phase dry-type encapsulated transformer (Type EP), and a secondary distribution load center with main breaker. Inter-connecting wiring is completed at the factory. Mini Power Centers are used wherever there is a 480V or 600V distribution system and loads requiring 208Y/120V, three-phase or 120/240V single-phase.

Read more: Mini Power Center


Autotransformer

autotransformers

Autotransformers are transformers which have a single winding per phase, part of which is common to both primary and secondary circuits. Using an Autotransformer is an economical and compact means of connecting electrical equipment to a power supply or a different voltage. Part of the winding is common to both primary and secondary circuits so there is no isolation between the two. This may be acceptable on some power systems that do not have a grounded neutral on the secondary side of the main power transformer. Typical applications include motor loads of industrial machinery, electric heating, air conditioners, etc. Designed for installation where a reliable power source is required for lighting and other low voltage equipment and machinery. Indoor and outdoor installation is possible depending on the enclosure.

Read more: Autotransformer


Industrial Control Transformer

Industrial control transformers are used to convert the available supply voltage to the voltage that is required to supply industrial control circuits and motor control loads.

These loads consist of a combination of electromagnetic devices such as solenoid operated valves, switches, bells, alarms, and other components such as indicator lights, timers, electronic equipment, and logic boards.

Some components of a circuit, especially electromagnetic devices require a very high level of power at start-up.  This start-up power requirement is called inrush VA. After their initial start-up, these components settle down to a lower power requirement for normal continuous operation. This lower operating power requirement is called Sealed or Steady State VA. Some devices can draw up to 10 times the normal operating or sealed current for periods of up to 50 milliseconds upon start up.

Control transformers must be designed, constructed, and selected to ensure that they provide the output voltage stability needed for trouble free operation of all circuit components.

Rex control transformers incorporate several features to optimize output voltage stability and regulation when supplying industrial control circuits with high inrush current requirements.

Read more: Industrial Control Transformer


Harmonic Mitigating Transformer

Harmonic Mitigating Transformers (HMT's) are specially designed for non-linear loads which draw significant amounts of harmonic current. While K-factor rated transformers are simply designed to handle the additional losses of supplying non-linear loads, HMT's actually minimize the voltage distortion and power losses that result from harmonic load currents.

Read more: Harmonic Mitigating Transformer


Encapsulated Transformer

Slide1

Encapsulated (Potted) Transformers (also referred to as Epoxy Resin Encapsulated) are designed for applications where the enviromental conditions would not permit a general purpose ventilated dry type transformer. The entire tranformer core & coil is encased in a silica sand / polyurethane mixture which protects the windings from any airborne contaminants and moisture.

Read more: Encapsulated Transformer


Cast Coil Power Transformer

Cast Coil2Cast coil power transformers feature primary and secondary windings which are vacuum cast inside a solid block of epoxy resin. The epoxy resin is introduced under vacuum in order to penetrate all the spaces within the winding, ensuring a void free casting with minimal partial discharges. The sold casting provides the highest degree of protection to the windings, making them ideally suitable for harsh environmental conditions which include airborne dust & high humidity. Furthermore, the fiberglass reinforcement which is incorporated into the casting provides the transformer with the highest mechanical strength which makes it resilient to short circuit forces.

Read more: Cast Coil Power Transformer


Motor Guarding Transient Filter

LineFilters catThe steep voltage wave fronts of the Pulse Width Modulated (PWM) output of Adjustable Frequency Drives (AFD’s) produce high frequency effects which may damage the insulation of motors operated by the equipment. The problems result from two distinct effects.

 

Read more: Motor Guarding Transient Filter


Air Core Reactor

ir-Core reactors provide a linear impedance with respect to current which is crucial in many applications where an iron core reactor would otherwise saturate.

Read more: Air Core Reactor


Control Power Transformer

Product Overview & Application

CPT webMedium Voltage Control Power Transformers (CPT) are single phase transformers used to supply control power in medium voltage switchgear and transformers. Nominal primary voltages range from 2.4kV to 15kV. The secondary voltage is typically configured for 120/240V (series parallel) operation. Note: Fuse and fuse clips shown in image are optional accessories.

Product Specification

Capacity  500VA to 3,000VA Single Phase
Voltage Class  up to 7.2kV (45kV BIL)
Cooling  Self Cooled (ANN / AN)
Frequency  60Hz (50/60Hz Optional)
Conductors  Copper (Cu) Windings
Insulation System  180°C (115°C rise) 
Enclosure Type            Open Construction With Encapsulated Coil
Warranty  12 Months (See Warranty and Limitations)
Quality System  ISO 9001:2015 Quality Management System
Certifications
  • CSA Certified
  • UL Listed
Reference Standards
  • CSA C22.2 No 47
  • CSA C22.2 No 66.1
  • CSA C9
  • IEEE C57.13.2
Optional Features & Accessories
  • Suitable For 50Hz Nominal Frequency
  • Primary Fuse Clips & Fuses

 

Documentation

Drawings


Drive Isolation Transformer

transformerDrive Isolation Transformers are designed for supplying power to SCR (Silicon Control Rectifier) motor drives which provide convenient variable speed motor control and can save on energy. Unfortunately, the drawback of these variable frequency drives (VFD) is that they produce harmonic voltage distortion and draw harmonic currents from the source which can be damaging both to the transformer supplying the power, and the other equipment that is connected to that supply.

 

Read more: Drive Isolation Transformer


VPI/VPE Power Transformer

CoreAndCoilVacuum Pressure Impregnated (VPI) power transformers utilize an open winding design, where the coil insulation is impregnated with an epoxy resin under vacuum and pressure, providing the windings a degree of protection against moisture and dirt, and improving the thermal conductivity of the winding which reduces localized hot spots. Furthermore, the VPI process removes air voids which deep within the windings, filling them with epoxy instead. These air voids, if not eliminated, can lead to higher partial discharges which can damage the transformer insulation over time, leading to premature failure. For a higher degree of protection, vacuum pressure encapsulated (VPE) coils can be utilized which involves repeated VPI and bake cycles

Read more: VPI/VPE Power Transformer


Encapsulated Transformer Enclosures

NEMA 3R Enclosures For Encapsulated Transformers (3 Phase)

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E3R-3PEP-1 11.00 10.00 15.25 23 PDF iconDWG iconSTP Icon
E3R-3PEP-2 15.00 11.00 15.25 33 PDF iconDWG iconSTP Icon
E3R-3PEP-3 18.00 12.50 17.00 41 PDF iconDWG iconSTP Icon
E3R-3PEP-4 21.00 14.00 17.50 49 PDF iconDWG iconSTP Icon
E3R-3PEP-5 21.00 18.00 20.00 68 PDF iconDWG iconSTP Icon
E3R-3PEP-6 26.00 18.00 25.00 85 PDF iconDWG iconSTP Icon
E3R-3PEP-7 32.00 18.00 30.00 114 PDF iconDWG iconSTP Icon
E3R-3PEP-8 36.00 25.00 32.00 154 PDF iconDWG iconSTP Icon
E3R-3PEP-9 36.00 25.00 36.00 167 PDF iconDWG iconSTP Icon

NEMA 3R Enclosures For Encapsulated Transformers (1 Phase)

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E3R-1PEP-1 5.25 4.50 11.00 4 PDF iconDWG iconSTP Icon
E3R-1PEP-2 6.00 5.25 12.00 5 PDF iconDWG iconSTP Icon
E3R-1PEP-3 7.50 6.50 13.50 8 PDF iconDWG iconSTP Icon
E3R-1PEP-4 12.50 12.50 15.00 33 PDF iconDWG iconSTP Icon
E3R-1PEP-5 15.00 15.00 18.00 43 PDF iconDWG iconSTP Icon
E3R-1PEP-6 18.00 14.00 25.00 57 PDF iconDWG iconSTP Icon
E3R-1PEP-7 19.00 16.00 28.00 68 PDF iconDWG iconSTP Icon
E3R-1PEP-8 25.00 20.00 33.00 100 PDF iconDWG iconSTP Icon
E3R-1PEP-9 25.00 22.00 36.00 110 PDF iconDWG iconSTP Icon

NEMA 4 Enclosures For Encapsulated Transformers (3 Phase)

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E4-3PEP-1 11.00 12.00 15.25 29 PDF iconDWG iconSTP Icon
E4-3PEP-2 15.00 13.00 15.25 37 PDF iconDWG iconSTP Icon
E4-3PEP-3 18.00 14.50 17.00 48 PDF iconDWG iconSTP Icon
E4-3PEP-4 21.00 16.00 17.50 62 PDF iconDWG iconSTP Icon
E4-3PEP-5 21.00 20.00 20.00 73 PDF iconDWG iconSTP Icon
E4-3PEP-6 26.00 20.00 25.00 95 PDF iconDWG iconSTP Icon
E4-3PEP-7 32.00 20.00 30.00 128 PDF iconDWG iconSTP Icon
E4-3PEP-8 36.00 27.00 32.00 164 PDF iconDWG iconSTP Icon
E4-3PEP-9 36.00 27.00 36.00 172 PDF iconDWG iconSTP Icon

NEMA 4 Enclosures For Encapsulated Transformers (1 Phase)

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E4-1PEP-1 7.75 7.00 11.50 7 PDF iconDWG iconSTP Icon
E4-1PEP-2 8.50 7.50 12.50 8 PDF iconDWG iconSTP Icon
E4-1PEP-3 10.00 9.00 14.00 11 PDF iconDWG iconSTP Icon
E4-1PEP-4 12.50 14.50 15.00 35 PDF iconDWG iconSTP Icon
E4-1PEP-5 15.00 17.00 18.00 47 PDF iconDWG iconSTP Icon
E4-1PEP-6 18.00 16.00 25.00 68 PDF iconDWG iconSTP Icon
E4-1PEP-7 19.00 18.00 28.00 79 PDF iconDWG iconSTP Icon
E4-1PEP-8 25.00 22.00 33.00 114 PDF iconDWG iconSTP Icon
E4-1PEP-9 25.00 24.00 36.00 125 PDF iconDWG iconSTP Icon

Distribution Transformer Enclosures

Standard NEMA 1 / 3R Ventilated Indoor Enclosures

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E1-0 9.50 7.00 8.00 7 PDF iconDWG iconSTP Icon
E1-1 12.00 9.00 9.30 11 PDF iconDWG iconSTP Icon
E1-2 11.00 11.00 14.00 21 PDF iconDWG iconSTP Icon
E1-3 15.50 11.00 14.00 24 PDF iconDWG iconSTP Icon
E3R-4 15.75 16.00 21.00 38 PDF iconDWG iconSTP Icon
E3R-5 20.50 16.00 25.00 48 PDF iconDWG iconSTP Icon
E3R-6 20.50 20.75 30.00 64 PDF iconDWG iconSTP Icon
E3R-7 24.50 21.75 36.00 86 PDF iconDWG iconSTP Icon
E3R-8 30.75 33.40 44.00 136 PDF iconDWG iconSTP Icon
E3R-8S 27.00 29.00 47.00 107 PDF iconDWG iconSTP Icon
E3R-9 40.00 38.00 52.00 211 PDF iconDWG iconSTP Icon
E3R-9S 32.00 32.00 52.00 158 PDF iconDWG iconSTP Icon
E3R-10 46.00 50.00 66.00 338 PDF iconDWG iconSTP Icon
E3R-11 60.00 55.00 70.70 400 PDF iconDWG iconSTP Icon
E3R-12 73.00 56.00 79.50 710 PDF iconDWG iconSTP Icon

Standard NEMA 3R Ventilated Outdoor Enclosures (c/w weather kit)

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E3R-2-W 11.00 16.10 14.00 23.5 PDF iconDWG iconSTP Icon
E3R-3-W 15.50 16.10 14.00 27.5 PDF iconDWG iconSTP Icon
E3R-4-W 15.75 21.10 21.00 42 PDF iconDWG iconSTP Icon
E3R-5-W 20.50 21.60 25.00 54 PDF iconDWG iconSTP Icon
E3R-6-W 20.50 26.40 30.00 69.5 PDF iconDWG iconSTP Icon
E3R-7-W 24.50 29.40 36.00 93.5 PDF iconDWG iconSTP Icon
E3R-8-W 30.75 37.50 44.00 145.5 PDF iconDWG iconSTP Icon
E3R-8S-W 27.00 30.00 47.00 115 PDF iconDWG iconSTP Icon
E3R-9-W 40.00 41.75 52.00 231 PDF iconDWG iconSTP Icon
E3R-9S-W 32.00 35.00 52.00 166 PDF iconDWG iconSTP Icon
E3R-10-W 46.00 50.00 66.00 353 PDF iconDWG iconSTP Icon
E3R-11-W 60.00 55.00 70.70 436 PDF iconDWG iconSTP Icon
E3R-12-W 73.00 56.00 79.50 750 PDF iconDWG iconSTP Icon

Standard NEMA 12 Ventilated Enclosures 

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E12-6 20.50 25.40 30.00 104 PDF iconDWG iconSTP Icon
E12-7 24.50 26.40 36.00 123 PDF iconDWG iconSTP Icon
E12-8 30.75 34.50 44.00 193 PDF iconDWG iconSTP Icon
E12-9 40.00 37.70 52.00 211 PDF iconDWG iconSTP Icon
E12-10 46.00 46.30 66.00 493 PDF iconDWG iconSTP Icon
E12-11 60.00 51.30 70.70 735 PDF iconDWG iconSTP Icon
E12-12 73.00 51.70 79.50 898 PDF iconDWG iconSTP Icon

Standard NEMA 4 Sealed Enclosures

Enclosure Size

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Downloads
E4-4 15.50 16.50 18.00 44 PDF iconDWG iconSTP Icon
E4-5 21.50 16.75 20.50 63 PDF iconDWG iconSTP Icon
E4-6 21.50 22.00 27.00 90 PDF iconDWG iconSTP Icon
E4-7 24.50 22.25 31.50 101 PDF iconDWG iconSTP Icon
E4-8 30.75 30.50 32.00 143 PDF iconDWG iconSTP Icon
E4-9 40.00 34.00 46.00 286 PDF iconDWG iconSTP Icon
E4-10 46.50 43.25 64.50 466 PDF iconDWG iconSTP Icon
E4-11 60.00 50.50 71.00 616 PDF iconDWG iconSTP Icon
E4-12 73.00 48.50 80.00 761 PDF iconDWG iconSTP Icon

Motor Starting Autotransformer

autotransformers

Motor starting autotransformers are a special transformers used in the autotransformer starting of a industrial motors. Autotransformer starting of motors is used widely in starting large industrial motors due to its advantage of providing the highest starting torque with lowest starting line current compared to other reduced voltage starting methods. The reduced voltage taps of the motor starting autotransformer are used to reduce the starting current of the transformer. Contactors switch between the taps, incrementally, increasing the votatge applied to motor as it gets up to speed, while ensuring the starting current is limited. Once the motor reached rated speed, the autotransformer is removed from the circuit entirely, avoiding any unnecessary energization losses. 

Read more: Motor Starting Autotransformer


Hazardous Location Transformer

Product Overview & Application

“Hazardous Locations and Harsh Industrial Environments” typically refers to areas which may contain dangerous and corrosive, explosive or combustible gases, liquids, or dust. Typical applications include mining, petrochemical, and pulp and paper industries. Rex Power Magnetics has been designing and producing a line of dry type transformers for Hazardous Locations and Harsh Industrial Environments. Rex’s product offering in this category includes three varieties, known as the HLA, HLB & HLC product lines, which are CSA and UL approved for CLASS I, DIVISION 2, GROUPS A, B, C, & D.

  • Group A: Atmospheres containing acetylene.
  • Group B: Atmospheres containing butadiene, ethylene oxide, hydrogen (or gases of vapors equivalent in hazard to hydrogen, such as manufactured gas) or propylene oxide.
  • Group C: Atmospheres containing acetaldehyde, cyclopropane, diethyl ether, ethylene, hydrogen sulfide, or unsymmetrical dimethyl hydrazine (UDHM), or other gases or vapors of equivalent hazard.
  • Group D: Atmospheres containing acetone, acrylonitrile, alcohol, ammonia, benzene, benzol, butane, ethylene, dichloride, gasoline, hexane, isoprene, lacquer solvent vapors, naphtha, natural gas, propane, propylene, styrene, vinyl acetate, vinyl chloride, xylenes, or other gases or vapors of equivalent hazard.

*NEW* A variant of Rex’s HLA & HLB transformers is available with IECEx approved CLASS 1 Zone 2 certification. Please contact our sales office for more information on IECEx approved transformers CLASS I, ZONE 2, GROUPS IIA, IIB, IIC 

  • Group II A: Atmospheres containing acetaldehyde, acetone, cyclopropane, alcohol, ammonia, benzene, benzol, butane, ethylene, dichloride, gasoline, hexane, isoprene, lacquer solvent vapors.
  • Group II B: Atmospheres containing acrylonitrile, butadiene, diethyl ether, ethylene, ethylene oxide, hydrogen sulfide, propylene oxide, or unsymmetrical dimethyl hydrazine (UDHM), or other gases or vapors of equivalent hazard.
  • Group II C: Atmospheres containing acetylene, carbon disulfide, hydrogen or other gases or vapors of equivalent hazard.

Product Specification

FEATURES TPYE HLA TYPE HLB TYPE HLC
Construction Features
  • ANC design
  • Encapsulated Transformer
  • Bottom/Front Access (based on kVA)
  • Conduit K/O on sides
  • nameplate marking
  • ANC design
  • Encapsulated Transformer
  • Bottom/Front Access (based on kVA)
  • Conduit K/O on sides
  • nameplate marking
  • ANC design
  • Ventilated Transformer
  • Bottom/Front Access (based on kVA)
  • Conduit O/O on sides
Insulation Class  200C  200C  220C
Temperature Rise  80C or 115C 80C or 115C  80C, 115C or 150C
Temperature Code  T3C or T3 T3C or T3  T3C, T3, or T2C
Enclosure
  • ASA #61 Grey
  • Type 3R outdoor
  • ASA #61 Grey
  • Type 3R outdoor
  • ASA #61 Grey
  • Type 3R outdoor
Certification CSA & UL approved for Class 1, Division2 CSA & UL approved for Class 1, Division2 CSA & UL approved for Class 1, Division2
Application Windings are encapsulated in epoxy, preventing airborne contaminants from reaching the coils, and thus preventing damage to the electrical insulation. As with HLA, the windings are encapsulated. Additionally, the connection between the leads and the coils are encapsulated. Wiring to the rest of the system is done at the leads. Conventional construction: non-encapsulated, vented design. Designed to conform to specified temperature code.

Documentation


K-Factor Rated Transformer

Today's modern electronic, electric components and circuitry such as computers, copiers, printers, fax machines and display terminals utilize switching mode power supplies for their operation. These switching mode power supplies are non-linear in nature and unlike a linear load which uses current from the power source continuously over the sinusoidal cycle, a non-linear load draws current in pulses from the power source thereby creating harmonic distortion. These harmonics currents cause significant power system problems such as:

  • Circuit breakers and fuses blowing far below current ratings
  • Neutrals in transformers and panel boards are much hotter than their ratings
  • Distributions Transformers are overheating even when operating well within their specified nameplate rating

Read more: K-Factor Rated Transformer


USA Sales Representative

USA Sales Representatives

 

Read more: USA Sales Representative


International Sales Reps

International Sales Representatives

 

Read more: International Sales Reps


Mexico Sales Representatives

MEXICO SALES REPRESENTATIVES

 

Read more: Mexico Sales Representatives