Control & Automation

Medium Voltage Control Power Transformers

Control & Automation

Medium Voltage Control Power Transformers

Agent Locator

Medium Voltage Control Power Transformers (CPT) are single phase transformers used to supply control power in medium voltage switchgear and transformers. Nominal primary voltages range from 2.4kV to 15kV. The secondary voltage is typically configured for 120/240V (series parallel) operation. Note: Fuse and fuse clips shown in image are optional accessories.

Capacity  500VA to 7,500VA Single Phase
Voltage Class  up to 15kV (60kV BIL)
Cooling  Air Cooled (ANN / AN)
Frequency  60Hz (50/60Hz Optional)
Conductors  Copper (Cu) Windings
Insulation System  180°C (115°C rise)
Enclosure Type  Open Construction With Encapsulated Coil
Warranty  12 Months (See Warranty and Limitations)
Quality System  ISO 9001:2015 Quality Management System
Certifications
  • CSA Certified: 7500VA, 15kV and 60 KV BIL
  • UL Recognized: 3000VA, 7.2kV and 60kV BIL
Reference Standards
  • CSA C22.2 No 47
  • CSA C9
  • CAN/CSA-C61869-1, -2, -3
  • IEEE C57.13.2
Optional Features & Accessories
  • Suitable For 50Hz Nominal Frequency
  • Primary Fuse Clips & Fuses

Dry-type transformers can generally be connected in reverse (back-fed), but there are some precautions to consider:

  • Compensated Windings: Control transformers and distribution transformers below 3kVA are typically designed with an overvoltage on the secondary to compensate for voltage regulation at full load. Reverse feeding these transformers may lead to a lower than expected output voltage.
  • Inrush current: The inrush current when energizing a transformer from the intended secondary terminals will be significantly higher than on the primary side as a multiple of the rated current. This high inrush current can cause nuisance tripping of the protective breaker and special considerations may need to be made.
  • Voltage Taps: Given that there are typically no voltage adjustment taps on the secondary side, the transformer cannot be adjusted to account for higher or lower than nominal incoming voltages. In order to not damage the insulation or overexcite the core, the input voltage should not exceed the nominal rated secondary voltage. In the case that the incoming voltage is lower than the nominal rated secondary voltage, the taps on the primary winding can be used to boost the output voltage.
  • Grounding: When the secondary (wye) of a delta-wye transformer is energized instead of the primary (delta), then the wye side of the transformer is not a separately derived service. As such, the neutral should not be connected to building ground nor should it be bonded to the transformer enclosure.

Always review applicable codes and standards and consult with the local authority having jurisdiction before reverse feeding transformers.

Shielded isolation transformers include a copper electrostatic shield between the primary and secondary windings, which helps reducing capacitive coupling between the windings, attenuating the transfer of high-frequency noise and transients from one system to the next. The primary advantages include superior noise suppression, improved protection against high-voltage spikes, and reduced risk of common-mode interference. The disadvantage is that shielded transformers can be more costly and larger in size compared to their non-shielded counterparts. In applications where high-frequency noise or voltage transients are a concern, the added investment in a shielded transformer is often justified.

Any transformer which is not installed and energized immediately should be stored in a dry, clean space having a uniform temperature to prevent condensation on the windings. Dry type transformers with resin dipped or epoxy vacuum impregnated coils can be stored at ambient temperatures as low as -50C. Transformers with encapsulated or epoxy cast coils should not be stored at ambient temperatures below -20C to prevent cracking of the epoxy. Preferably, transformers should be stored in a heated building having adequate air circulation and protected from cement, plaster, paint, dirt, and water or other gases, powders, and dust. The floor on which the transformer is being stored should be resistant to the upward migration of water vapor. Precautions should be taken to prevent storage in an area that water could be present, such as roof leaks, windows, etc. Condensation or absorption of moisture can be greatly reduced by keeping the transformer enclosure 5⁰C-10⁰C above ambient temperature. This can be easily achieved by the installation and energization of space heaters (optional). If the transformer is not furnished with internal space heaters, then external, portable heaters can be used. Note: Lamps or heaters should never come in direct contact with the transformer coil insulation.

It is not advisable to store a dry type transformer outdoors, but in the case that it is unavoidable, protective measures should be taken to prevent moisture and foreign debris from entering the transformer enclosure. The plastic wrapping supplied during shipment should be left in place, and a suitable drying agent such as silica gel packs should be used. The unit should also be checked periodically for indications of condensation on the windings, coil support blocks, core, core clamping system and bus/cables.

Unless designed for special service conditions / environments, below are the standard service conditions for dry type distribution transformers:

  • Ambient Temperature: -40°C to + 30°C (max peak +40°C)
  • Relative Humidity: less than 70%
  • Altitude: up to 1000m (3300 ft.) above seal level

To ensure proper operation, avoid installing transformers in environments with excessive moisture, extreme temperatures, or direct sunlight. Maintain recommended clearances and keep all ventilation panels unobstructed.

The minimum required clearances of a dry type transformer to walls, floors or other equipment must adhere to the local electrical code requirements.

In the absence of such requirements, Rex Power Magnetics recommends that dry type transformers be mounted so that there is an air space of no less than 150mm (6”) between the enclosures, and between the enclosure and any adjacent surface except floors. When the adjacent surface is a combustible material, the minimum permissible separation between the transformer enclosure and the adjacent surface should be 300mm (12”). Where the adjacent surface is the wall on which the transformer is mounted, the minimum permissible separation between the enclosure and the mounting wall should be 6mm (0.25”) so long as the surface is of a non-combustible material.

In dry-type transformers, the surrounding air plays a critical role in their operation. Generally, low ambient temperatures do not negatively impact an energized transformer, as the no-load losses typically generate enough heat to maintain proper conditions, even in environments as cold as -40°C. However, transformers stored at low temperatures present two primary concerns:

  • Insulation Brittleness: At low temperatures, the insulation in the coils may become brittle. Expanding conductors when a cold transformer is loaded, or contracting conductors during cold storage, may cause cracks in the insulation, leading to internal faults.
  • Condensation Risk: Low temperatures can cause condensation inside the transformer enclosure, as well as on the transformer coils. Energizing a transformer with condensation present on the coils can lead to internal faults and insulation damage.

Rex Power Magnetics recommends testing transformers (megger testing), warming them to above 0°C, or following a drying-out procedure if moisture is suspected. Refer to Rex Power Magnetics’ cold start procedures to ensure safe energization in cold conditions. Energizing a transformer with compromised insulation due to moisture can cause damage and potential safety hazards.

Cold Start Procedure

The life expectancy of a dry-type transformer is primarily determined by the insulation system and the operating temperature. According to IEEE Std. C57.96, the deterioration of insulation is directly related to the time and temperature the transformer experiences during operation. Insulation materials degrade faster at higher temperatures, so the transformer’s life expectancy is closely tied to how well it is kept within its design temperature limits.

In most transformers, the highest temperature occurs at a specific point in the windings, known as the hot spot. This area undergoes the most significant wear over time, making it the primary factor in determining the transformer’s ageing process.

All of Rex Power Magnetics’ dry-type transformers are designed using UL-listed insulation systems with a maximum hot spot temperature that ensures a design life of at least 30 years under standard operating conditions (continuous rated load, typical ambient temperatures, and no sustained overloads). Transformers designed with reduced temperature rise can extend this design life expectancy to over 50 years, as operating at lower temperatures slows the insulation’s ageing process.

Factors That Affect Life Expectancy:

  • Temperature: As discussed, the most significant factor is the operating temperature of the transformer. Operating continuously at higher temperatures reduces the expected lifespan.
  • Humidity and Condensation: Humid environments or condensation can affect the insulation material and lead to premature failure. Proper storage and maintenance help mitigate this risk.
  • Short Circuit Events: Sudden surges or short circuits can damage internal components and shorten the transformer’s life.
  • Overloading: Continuous overloading beyond the transformer’s rated capacity generates excess heat, which accelerates insulation degradation.
  • Environmental Conditions: Extreme environments, such as exposure to dust, moisture, or chemicals, can also lead to earlier-than-expected failure.

By following proper installation and maintenance practices, such as avoiding overloading and ensuring the transformer operates within its designed ambient temperature, you can significantly extend its lifespan. Rex Power Magnetics’ high-quality transformers are built for durability, ensuring reliable performance for decades under standard conditions.

It`s normal for new transformers to release some harmless odors from the varnish impregnation used in the coils for a week or two after energization. Older Transformers can also release some odor if loaded to a higher level than they have experienced previously in their history.

Rex Power Magnetics’ ventilated distribution transformer terminals are rated 90°C. Conductors with at least a 90°C insulation rating at or below their 90°C ampacity rating should be utilized.

Canadian dry-type transformer design and manufacturing company

Get Quote