Medium Voltage Power Transformers

VPI/VPE Power Transformers

Medium Voltage Power Transformers

VPI/VPE Power Transformers

Agent Locator

Vacuum Pressure Impregnated (VPI) power transformers utilize an open winding design, where the coil insulation is impregnated with an epoxy resin under vacuum and pressure, providing the windings a degree of protection against moisture and dirt, and improving the thermal conductivity of the winding which reduces localized hot spots. Furthermore, the VPI process removes air voids which deep within the windings, filling them with epoxy instead. These air voids, if not eliminated, can lead to higher partial discharges which can damage the transformer insulation over time, leading to premature failure. For a higher degree of protection, vacuum pressure encapsulated (VPE) coils can be utilized which involves repeated VPI and bake cycles. The VPE process builds a thick coat of epoxy over the windings which increases the windings resilience in humid and dirty environments.

Rex Vacuum Pressure Impregnated (VPI) dry type power transformers are primarily designed for stepping down high voltages from transmission and distribution systems to lower voltages which can be utilized in commercial, industrial, institutional or utility applications. They are ideally suited for both indoor and outdoor applications and require minimal maintenance to provide many years of reliable trouble free service. Unlike liquid filled transformers which are cooled with oil or a fire resistant liquid dielectric, dry type units utilize only environmentally safe, CSA and UL recognized high temperature insulation systems. Dry type designs provides a safe and reliable power source which does not require fire proof vaults, catch basins or the venting of toxic gasses. These important safety factors allow the installation of dry type transformers inside buildings close to the load, which improves overall system regulation and reduces costly secondary line losses.

Typically, dry type transformers are designed in one of the following three configurations:

1. General Purpose Power Transformer

General purpose power transformers are designed with primary and secondary bus stubs terminals suitable for side or bottom cable entry directly into the transformer enclosure. The terminals are mounted in a “stubs up” or “stubs down” configuration and electricians route the incoming and outgoing cables directly to these terminals. Optionally, the bus terminals can be routed to the either end of the enclosure to reduce the amount of internal cable routing required on site. For top cable entry applications, the terminals may be routed to an air terminal chamber (ATC).

2. Unit Substation Transformer

UnitSubstationUnit substation transformers are designed for close coupling with primary and/or secondary equipment. Transformer terminals are bussed to the either end of the transformer, and their exact location is coordinated with the equipment the transformer will be integrating with. The enclosure end walls feature openings which line up with the primary and/or secondary equipment, and flex connector can be utilized to connect the transformer with the other equipment. Unit substations are ideal for reducing the required space in an electrical room as the equipment can be installed right up against one another without the need for transition cells.

3. Pad Mounted Transformer

PadMountPad mounted transformers feature a compartmentalized design with front accessible and pad lockable primary and secondary air terminal chambers. These configurations are particularly well suited for outdoor areas with underground incoming and outgoing power service where the general public may be present. Transformer voltage taps are accessible from the rear via a removable panel or pad lockable door and tamperproof enclosure hardware is utilized to deter forced entry.

Rex Power Magnetics has over 30 years of experience designing and manufacturing medium voltage power transformers to meet various requirements and applications which include:

  • Zig Zag Grounding Transformers
  • Single Phase Neutral Grounding Transformers
  • Triplex Configuration Transformers
  • Transformers for Mining, Pulp and Paper Application
  • Corrosion Resistant Transformers for Marine Applications
  • Low Electromagnetic Field Emission Transformers For Hospital and Institutional Use
  • Traction Power Rectifier Transformers for Transit Systems
  • Motor Starting & Drive System Applications
  • High Harmonic and Intermittent Load Applications

Our technical team is always ready to find a solution and design a custom transformer for the most challenging applications.

Capacity  100 to 5,000 kVA Single Phase and 300 to 15,000 kVA Three Phase
Voltage Class  up to 46kV (250kV BIL)
Cooling  Air Cooled (ANN) [Optional Forced Air Cooled (AFN/AF)]
Frequency  60Hz [50/60Hz Optional]
Conductors  Copper (Cu) or Aluminum (Al) Windings
Insulation System  220°C (150°C Temperature Rise) [Optional 115°C & 80°C Rise Available]
Impregnation  Epoxy Vaccum Pressure Impregnated (VPI) and Baked [Optional VPE]
Efficiency  Meets North American Energy Efficiency Standards:

  • U.S. – (DOE 2016) DOE 10 CFR Part 431
  • Canada – (NRCan 2019) SOR/2018-201, Amd. 14 & ON Reg. 404/12
Primary Taps  Typically +/-2 x 2.5% taps
Sound Level  Meets IEEE C57.12.01
Configuration  Terminal Bus Stubs Suitable For Cables [Optional Unit-Substation or Padmount Configuration]
Enclosure Type  Type 1 Indoor [Type 2, 3R, 4, 4X & 12 Optional]
Enclosure Finish  ANSI 61 Grey Powder Coat
Testing  Std Production Tests (per IEEE C57.12.91)

  • Winding Resistance
  • Turns Ratio
  • Polarity and Phase Relation
  • No-Load Loss and Excitation Current
  • Load Loss & Impendance
  • Applied Potential
  • Induced Potential
 Optional Type Tests

  • Basic Insulation Level (BIL)
  • Temperature Rise (Heat Run)
  • Sound Level
  • Partial Discharge

Other Optional Tests

  • RIV
  • Power Factor
Warranty  18 Months (See Warranty and Limitations)
Quality System  ISO 9001:2015 Quality Management System
Certifications
  • CSA Certified
  • UL Listed
Reference Standards
  • CSA C22.2 No 47
  • CSA C9
  • IEEE C57.12.01
  • IEEE C57.12.91
Optional Features & Accessories
  • Provision for Future Fans or Fan Packages (AFN) completely installed with or without Control Power
  • Buss Co-ordination with primary and secondary switchgear (Unit-Substation configuration)
  • Dial (Analog) or Digital Thermometers to monitor winding temperatures
  • Neutral Ground Resistors (NGR) and Monitoring
  • Anti-Condensation Strip Heaters
  • Switching surge mitigating R.C. Snubbers (with or without ground current monitoring)
  • Ground Fault Protection Relays (GFR)
  • Anti-Vibration mounting to reduce transformer hum (sound level)
  • Provision for Seismic mounting or complete Seismic Snubbers and Restraints
  • Distribution, Intermediate or Station Class Surge Arrestors
  • Provision for Buss Duct Entry
  • Fully Insulated Buss
  • Mimic Buss
  • Kirk-Key Interlock

Drawings of 150°C or 115°C Rise, Stubs Up, Max. 600V/10kV BIL on L.V.

BIL 10kV 30kV 45kV 60kV 95kV 125kV 150kV
Rating 1.2kV Class 5.0kV Class 8.7kV Class 15.0kV Class 18.0kV Class 25kV Class 34.5kV Class
225kVA E3R-9-W E3R-10-W E3R-10-W E3R-11-W E3R-12-W Special Special
300kVA E3R-9-W E3R-10-W E3R-10-W E3R-11-W E3R-12-W Special Special
450kVA E3R-10-W E3R-11-W E3R-11-W E3R-12-W E3R-13-W E3R-16-W Special
500kVA E3R-10-W E3R-11-W E3R-12-W E3R-12-W E3R-13-W E3R-16-W E3R-17-W
600kVA E3R-11-W E3R-11-W E3R-12-W E3R-12-W E3R-13-W E3R-16-W E3R-17-W
750kVA E3R-11-W E3R-12-W E3R-12-W E3R-12-W E3R-14-W E3R-17-W E3R-18-W
1,000kVA E3R-12-W E3R-12-W E3R-13-W E3R-13-W E3R-16-W E3R-17-W E3R-19-W
1,250kVA E3R-13-W E3R-13-W E3R-13-W E3R-14-W E3R-17-W E3R-19-W E3R-19-W
1,500kVA E3R-13-W E3R-13-W E3R-13-W E3R-14-W E3R-17-W E3R-18-W E3R-20-W
1,750kVA E3R-14-W E3R-14-W E3R-14-W E3R-14-W E3R-17-W E3R-18-W E3R-20-W
2,000kVA E3R-14-W E3R-14-W E3R-14-W E3R-14-W E3R-17-W E3R-18-W E3R-21-W
2,250kVA E3R-14-W E3R-14-W E3R-14-W E3R-17-W E3R-17-W E3R-19-W E3R-21-W
2,500kVA E3R-14-W E3R-14-W E3R-14-W E3R-17-W E3R-18-W E3R-19-W E3R-21-W
3,000kVA E3R-15-W E3R-15-W E3R-16-W E3R-17-W E3R-18-W E3R-21-W E3R-22-W
3,500kVA Special E3R-19-W E3R-19-W E3R-20-W E3R-21-W E3R-21-W E3R-22-W
3,750kVA Special E3R-19-W E3R-19-W E3R-20-W E3R-21-W E3R-21-W E3R-22-W
4,000kVA n/a E3R-20-W E3R-20-W E3R-20-W E3R-21-W E3R-21-W E3R-22-W
4,500kVA n/a E3R-21-W E3R-21-W E3R-21-W E3R-21-W E3R-22-W E3R-23-W
4,750kVA n/a E3R-21-W E3R-21-W E3R-21-W E3R-21-W E3R-22-W E3R-23-W
5,000kVA n/a E3R-21-W E3R-21-W E3R-21-W E3R-21-W E3R-22-W E3R-23-W
Photos
Videos

Shielded isolation transformers include a copper electrostatic shield between the primary and secondary windings, which helps reducing capacitive coupling between the windings, attenuating the transfer of high-frequency noise and transients from one system to the next. The primary advantages include superior noise suppression, improved protection against high-voltage spikes, and reduced risk of common-mode interference. The disadvantage is that shielded transformers can be more costly and larger in size compared to their non-shielded counterparts. In applications where high-frequency noise or voltage transients are a concern, the added investment in a shielded transformer is often justified.

Unless designed for special service conditions / environments, below are the standard service conditions for dry type distribution transformers:

  • Ambient Temperature: -40°C to + 30°C (max peak +40°C)
  • Relative Humidity: less than 70%
  • Altitude: up to 1000m (3300 ft.) above seal level

To ensure proper operation, avoid installing transformers in environments with excessive moisture, extreme temperatures, or direct sunlight. Maintain recommended clearances and keep all ventilation panels unobstructed.

Any transformer which is not installed and energized immediately should be stored in a dry, clean space having a uniform temperature to prevent condensation on the windings. Dry type transformers with resin dipped or epoxy vacuum impregnated coils can be stored at ambient temperatures as low as -50C. Transformers with encapsulated or epoxy cast coils should not be stored at ambient temperatures below -20C to prevent cracking of the epoxy. Preferably, transformers should be stored in a heated building having adequate air circulation and protected from cement, plaster, paint, dirt, and water or other gases, powders, and dust. The floor on which the transformer is being stored should be resistant to the upward migration of water vapor. Precautions should be taken to prevent storage in an area that water could be present, such as roof leaks, windows, etc. Condensation or absorption of moisture can be greatly reduced by keeping the transformer enclosure 5⁰C-10⁰C above ambient temperature. This can be easily achieved by the installation and energization of space heaters (optional). If the transformer is not furnished with internal space heaters, then external, portable heaters can be used. Note: Lamps or heaters should never come in direct contact with the transformer coil insulation.

It is not advisable to store a dry type transformer outdoors, but in the case that it is unavoidable, protective measures should be taken to prevent moisture and foreign debris from entering the transformer enclosure. The plastic wrapping supplied during shipment should be left in place, and a suitable drying agent such as silica gel packs should be used. The unit should also be checked periodically for indications of condensation on the windings, coil support blocks, core, core clamping system and bus/cables.

The minimum required clearances of a dry type transformer to walls, floors or other equipment must adhere to the local electrical code requirements.

In the absence of such requirements, Rex Power Magnetics recommends that dry type transformers be mounted so that there is an air space of no less than 150mm (6”) between the enclosures, and between the enclosure and any adjacent surface except floors. When the adjacent surface is a combustible material, the minimum permissible separation between the transformer enclosure and the adjacent surface should be 300mm (12”). Where the adjacent surface is the wall on which the transformer is mounted, the minimum permissible separation between the enclosure and the mounting wall should be 6mm (0.25”) so long as the surface is of a non-combustible material.

In dry-type transformers, the surrounding air plays a critical role in their operation. Generally, low ambient temperatures do not negatively impact an energized transformer, as the no-load losses typically generate enough heat to maintain proper conditions, even in environments as cold as -40°C. However, transformers stored at low temperatures present two primary concerns:

  • Insulation Brittleness: At low temperatures, the insulation in the coils may become brittle. Expanding conductors when a cold transformer is loaded, or contracting conductors during cold storage, may cause cracks in the insulation, leading to internal faults.
  • Condensation Risk: Low temperatures can cause condensation inside the transformer enclosure, as well as on the transformer coils. Energizing a transformer with condensation present on the coils can lead to internal faults and insulation damage.

Rex Power Magnetics recommends testing transformers (megger testing), warming them to above 0°C, or following a drying-out procedure if moisture is suspected. Refer to Rex Power Magnetics’ cold start procedures to ensure safe energization in cold conditions. Energizing a transformer with compromised insulation due to moisture can cause damage and potential safety hazards.

Cold Start Procedure

The life expectancy of a dry-type transformer is primarily determined by the insulation system and the operating temperature. According to IEEE Std. C57.96, the deterioration of insulation is directly related to the time and temperature the transformer experiences during operation. Insulation materials degrade faster at higher temperatures, so the transformer’s life expectancy is closely tied to how well it is kept within its design temperature limits.

In most transformers, the highest temperature occurs at a specific point in the windings, known as the hot spot. This area undergoes the most significant wear over time, making it the primary factor in determining the transformer’s ageing process.

All of Rex Power Magnetics’ dry-type transformers are designed using UL-listed insulation systems with a maximum hot spot temperature that ensures a design life of at least 30 years under standard operating conditions (continuous rated load, typical ambient temperatures, and no sustained overloads). Transformers designed with reduced temperature rise can extend this design life expectancy to over 50 years, as operating at lower temperatures slows the insulation’s ageing process.

Factors That Affect Life Expectancy:

  • Temperature: As discussed, the most significant factor is the operating temperature of the transformer. Operating continuously at higher temperatures reduces the expected lifespan.
  • Humidity and Condensation: Humid environments or condensation can affect the insulation material and lead to premature failure. Proper storage and maintenance help mitigate this risk.
  • Short Circuit Events: Sudden surges or short circuits can damage internal components and shorten the transformer’s life.
  • Overloading: Continuous overloading beyond the transformer’s rated capacity generates excess heat, which accelerates insulation degradation.
  • Environmental Conditions: Extreme environments, such as exposure to dust, moisture, or chemicals, can also lead to earlier-than-expected failure.

By following proper installation and maintenance practices, such as avoiding overloading and ensuring the transformer operates within its designed ambient temperature, you can significantly extend its lifespan. Rex Power Magnetics’ high-quality transformers are built for durability, ensuring reliable performance for decades under standard conditions.

It`s normal for new transformers to release some harmless odors from the varnish impregnation used in the coils for a week or two after energization. Older Transformers can also release some odor if loaded to a higher level than they have experienced previously in their history.

Rex Power Magnetics’ ventilated distribution transformer terminals are rated 90°C. Conductors with at least a 90°C insulation rating at or below their 90°C ampacity rating should be utilized.

Voltage regulation refers to the voltage drop on the secondary side of the transformer from no load to full load. The voltage drop is a function of the percentage loading and the power factor of the load. Low voltage distribution isolation transformers generally have a voltage regulation which will range between 1-3% at full load for load with a power factor of 1, and 2-5% at full load for load with a power factor of 0.8.

Canadian dry-type transformer design and manufacturing company

Get Quote